Final | 6/2/2017 | 6/5/2017 | 6/5/2017 | A | PASS |
Tom Saunders
|
|
|
Original final requested for Fri PM, inspector was there in AM due to a schedule conflict. Tom S. directed couple of corrections which are done. Inspector requested return inspection for Monday instead of Fri afternoon. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot...
corrections made...ok to final
|
Final | 6/2/2017 | 6/2/2017 | 6/2/2017 | P | CANC |
Tom Saunders
|
|
|
Corrections will be complete by 1:00, if not earlier. Dustin will call Tom S. and advise him. Thank you Phone #: ###-#### >> Inspection requested via web by Paula Gratiot Inspection cancelled from web by: Paula Gratiot
|
Final | 6/1/2017 | 6/2/2017 | 6/2/2017 | P | FAIL |
Tom Saunders
|
|
|
Should be unlocked. Builder phone is Greg ###-####. ESW phone is ###-#### Dustin is ###-#### Phone #: ###-#### Inspection requested via web by Paula Gratiot....
dwn stairs closet has 2 outlets needing gfi protection...uninhabitable area
hot tub circuit shall have gfi protection...in panel or at junction box/disconnect
dishwasher circuit shall have lock out installed
microwave circuit shall have lock out instaleed
|
Rough-In Permanent Service | 1/5/2017 | 1/6/2017 | 1/6/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot....
rough ok to cover house and shop p/s u/g n ok
|