Final | 4/24/2017 | 4/25/2017 | 4/25/2017 | A | PASS |
James Ady
|
|
|
Code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman corrections made final ok
|
Final | 4/20/2017 | 4/24/2017 | 4/24/2017 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman 110.3- Devices shall be wired as per manufacturers instructions. 4 receptacles not working in theater, pantry light not working, all outdoor receptacles have reverse polarity. 210.52(C)- No point on kitchen counter shall be more than 24" from a receptacle. Counter by window 6' 4" between recepts. 210.52(D)- Master vanity receptacles serving basins shall be located on wall or cabinet adjacent to basin. 422.30- Range hood shall have an accessible disconnecting means. 110.25 lockout acceptable.
|
Electrical Rough-In | 3/14/2017 | 3/15/2017 | 3/15/2017 | A | PASS |
James Ady
|
|
|
Floor heat Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman master floor heat only rough in ok
|
Rough-In Permanent Service | 1/23/2017 | 1/24/2017 | 1/24/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman rough in ok p/s u/g n ok
|