Permit Information
Permit NumberELE17-00447
StatusFinaled
Name L & K ELECTRIC
Site Address 2212 N 20TH ST
Project Name 
Customer Number8087
ePlanReviewNo
Description
Alteration or Repair: Rewire house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/26/20174/27/20174/27/2017APASS
DetailsMark Moncarr
Electrician questions ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Corrections made. Ok final
Final4/25/20174/25/20174/25/2017PFAIL
DetailsMark Moncarr
Call Michael Donelson with any questions ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
1. Misc outlets throughout house need to be tamper resis.
2. Wire a little tight at end of wiremold above downstairs fireplace.
3. Spark ring needed for upstairs fireplace outlet.
4. Outlet on E. wall in garage not GFI protected.
5. Junction box in downstairs SE bedroom closet needs to stay accessible, cannot close in wall.
Permanent Service3/15/20173/16/20173/16/2017APASS
DetailsMark Moncarr
Service Inspection. Call Michael Donelson with any questions. ###-####. Phone #: ###-#### Inspection requested via web by Samatha Solberg Mast was raised and appears to be right at around 22.5 feet over perimeter of pool. IDP may need to tighten overhead drop if possible
Temporary Service3/13/20173/14/20173/14/2017PFAIL
DetailsMark Moncarr
Please Call Mike Donelson ###-#### to let him know when you will be there so he can meet you for a service inspection and a consultation. Phone #: ###-#### Inspection requested via web by Samatha Solberg. Might need to get with IDP to see if they can tighten overhead conductors enough to gain 22.5' clearence for pool. Horizontal limit for overhead conductors from waters edge of pool is 10'.
Electrical Rough-In3/6/20173/6/20173/6/2017PPASS
DetailsTom Saunders
Rough in for down stairs. ###-#### if you have questions. Phone #: ###-#### Inspection requested via web by Samatha Solberg...

rough in downstairs ok to cover....1 outlet in downstairs bed needs added...check at final
Electrical Rough-In2/22/20172/23/20172/23/2017PPASS
DetailsMark Moncarr
This a partial rough in inspection for the upstairs only. Electrician: David Joseph ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Ok cover upstairs walls only