Final | 3/16/2017 | 3/16/2017 | 3/16/2017 | P | PASS |
Rock A. Hudson
|
|
|
Per discussion receptacle was not installed. Phone #: ###-#### Inspection requested via web by Kelly Tarter Final ok
|
Permanent Service | 3/16/2017 | 3/16/2017 | 3/16/2017 | P | PASS |
Rock A. Hudson
|
|
|
Per discussion receptacle was not installed. Phone #: ###-#### Inspection requested via web by Kelly Tarter p/s u/g n ok
|
Final | 3/10/2017 | 3/13/2017 | 3/13/2017 | A | FAIL |
Rock A. Hudson
|
|
|
We will not be onsite. Please call if you have any questions. Thank you. Phone #: ###-#### Inspection requested via web by Kelly Tarter 110.24- Available fault current shall be posted. 210.64- A 15 or 20 amp 120 volt receptacle outlet shall be located within 50' of service. 250.28(C)- Main bonding jumper screw not tight.
|
Electrical Rough-In | 3/7/2017 | 3/7/2017 | 3/7/2017 | P | PASS |
Tom Saunders
|
|
|
U.G. inspection for cover. Please contact Bob at number listed. Phone #: ###-#### Inspection requested via web by Kelly Tarter...
U/G ok to cover....eastside parking lot-Discovery center
|