Final | 6/9/2017 | 6/12/2017 | 6/12/2017 | A | PASS |
Rock A. Hudson
|
|
|
Garage code 1624 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Final | 6/1/2017 | 6/1/2017 | 6/1/2017 | P | FAIL |
James Ady
|
|
|
garage code 1624 Phone #: ###-#### Inspection requested via web by Darryn Coburn Back room by Dining needs AFCI protection and Smoke detector. 2 receps back wall of Dining read open nuetral. Weather proof by A/C not trimmed out. Back patio weather proof dead. Put lock out on Furnace
|
Rough-In Permanent Service | 3/14/2017 | 3/15/2017 | 3/15/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made. Rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 3/13/2017 | 3/14/2017 | 3/14/2017 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Damaged wire above range hood and loop pulled out of wall in up hall bath
|