Final | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | CANC |
Tom Saunders
|
|
|
Access 6021 Phone #: ###-#### Inspection requested via web by David Nelson....scheduled multiple times
|
Final | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | CANC |
Tom Saunders
|
|
|
Access 6021 Phone #: ###-#### Inspection requested via web by David Nelson..scheduled multiple times
|
Final | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | PASS |
Tom Saunders
|
|
|
Access 6021 Phone #: ###-#### Inspection requested via web by David Nelson...corrections made...ok to final...also finalled is permit ELE17-02613 which is for complete rewire of house
|
Final | 10/24/2017 | 10/25/2017 | 10/25/2017 | A | FAIL |
Tom Saunders
|
|
|
access 6021 Phone #: ###-#### Inspection requested via web by David Nelson... 1) listed cover used to hook up water htr-110.3B 2) downstairs bedroom lights not working-110.7 3) exposed wires in down stairs bed light-110.7 4) downstairs closet light to close to shelf-410.16(C) 5) open can trims in master closet-410.16(B) 6) hood has no power-110.7 7) microwave circuit needs breaker lock out 8) GFI in garage shall be firmly attached to box-406.5
|
Permanent Service | 3/14/2017 | 3/15/2017 | 3/15/2017 | A | PASS |
Tom Saunders
|
|
|
representative will be on site all morning Phone #: ###-#### Inspection requested via web by David Nelson...
p/s rec ok
|