Final | 10/4/2017 | 10/4/2017 | 10/4/2017 | A | PASS |
Daryl DeGrange
|
|
|
hired a different company Phone #: ###-#### Trim out stage being completed by ELE17-02796
|
Rough-In Permanent Service | 3/23/2017 | 3/23/2017 | 3/23/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Have till 3/27 to fix 50A GFCI Temp. Rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 3/22/2017 | 3/22/2017 | 3/22/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3 440.6- Furnace in garage shall have supply of 20 amp circuit nd 12 ga. wire minimum as per manufacturers instructions. 210.52- Wall space shall have receptacle outlets located so no point measured along floor line is more than 6' from receptacle. Down bed, within 6' of pocket door, Up loft along family room rail. 300.4- MN cable shall not be installed where subject to physical damage. Both fireplace location NM cable near flue. Nail plate ENT above panel. 314.17- Open knock out in bath fan box shall be closed. 314.25- Master shower can secure box cover. 590.6- 50 amp temp receptacle, GFCI not working.
|