ELE-Aging Inspection | 4/13/2020 | 4/13/2020 | 4/13/2020 | | PASS |
Mark Moncarr
|
|
|
Met onsite with business owner. All corrections were made regarding GFI protection in patient areas by sinks.
|
Final | 4/13/2020 | 4/13/2020 | 4/13/2020 | A | PASS |
Mark Moncarr
|
|
|
Met with business owner of dental office at a prearranged time as per phone call. All corrections were made as far as GFI protection in patient areas by sinks.
|
ELE-Aging Inspection | 1/13/2020 | 1/13/2020 | 1/13/2020 | | DONE |
Mark Moncarr
|
|
|
I coordinated with Dental office to verify GFI protection was installed in patient areas. Scheduled to meet at 2pm Friday the 17th of Jan.
|
ELE-Aging Inspection | 10/14/2019 | 10/14/2019 | 10/17/2019 | | FAIL |
Mark Moncarr
|
|
|
Job was failed on 7/25/17 for GFI protection in patient areas. Have notified contractor a few times that a final was needed. Have had no response. I am turning it over to the Legal Department at this time.
|
ELE-Aging Inspection | 7/15/2019 | 7/15/2019 | 7/15/2019 | | FAIL |
Mark Moncarr
|
|
|
We need to schedule a final inspection. Coordinate a time, so GFI's can be checked.
|
ELE-Aging Inspection | 4/15/2019 | 4/15/2019 | 4/18/2019 | | DONE |
Mark Moncarr
|
|
|
Please schedule a final inspection to meet on-site and check GFI"s.
|
Final | 7/25/2017 | 7/26/2017 | 7/26/2017 | P | CANC |
Mark Moncarr
|
|
|
Corey Phone #: ###-####
|
Final | 7/25/2017 | 7/25/2017 | 7/25/2017 | P | FAIL |
Mark Moncarr
|
|
|
corey Phone #: ###-#### All areas in question are considered Category 3 Basic Care Space. Category 1 does not require GFI protection. 517.21 states this. All other Category classifications require GFI protection as per 517.21 commentary that reverts to 210.8(B), GFI protection for personnel.
|
Electrical Rough-In | 6/27/2017 | 6/28/2017 | 6/28/2017 | A | PASS |
Mark Moncarr
|
|
|
Cory Phone #: ###-#### Ok cover front half of re-model. All existing wiring demo, and new MC installed including redundant where needed.
|
Final | 5/26/2017 | 5/26/2017 | 5/26/2017 | P | PART |
Mark Moncarr
|
|
|
partial final Phone #: ###-#### Ok PARTIAL final. Waiting for small DW for new side. Wires are safed off.
|
Conference | 3/27/2017 | 3/28/2017 | 3/28/2017 | A | PASS |
Mark Moncarr
|
|
|
Corey Phone #: ###-#### Supposed to a RI cover. Ok cover
|