Permit Information
Permit NumberELE17-00806
StatusFinaled
Name COREY REA ELECTRICAL SERVICES
Site Address 813 N STILSON RD
Project NameParkway Dental - Remodel
Customer Number 
ePlanReviewNo
Description
Remodel-move and update existing electrical system
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection4/13/20204/13/20204/13/2020 PASS
DetailsMark Moncarr
Met onsite with business owner. All corrections were made regarding GFI protection in patient areas by sinks.
Final4/13/20204/13/20204/13/2020APASS
DetailsMark Moncarr
Met with business owner of dental office at a prearranged time as per phone call. All corrections were made as far as GFI protection in patient areas by sinks.
ELE-Aging Inspection1/13/20201/13/20201/13/2020 DONE
DetailsMark Moncarr
I coordinated with Dental office to verify GFI protection was installed in patient areas. Scheduled to meet at 2pm Friday the 17th of Jan.
ELE-Aging Inspection10/14/201910/14/201910/17/2019 FAIL
DetailsMark Moncarr
Job was failed on 7/25/17 for GFI protection in patient areas. Have notified contractor a few times that a final was needed. Have had no response. I am turning it over to the Legal Department at this time.
ELE-Aging Inspection7/15/20197/15/20197/15/2019 FAIL
DetailsMark Moncarr
We need to schedule a final inspection. Coordinate a time, so GFI's can be checked.
ELE-Aging Inspection4/15/20194/15/20194/18/2019 DONE
DetailsMark Moncarr
Please schedule a final inspection to meet on-site and check GFI"s.
Final7/25/20177/26/20177/26/2017PCANC
DetailsMark Moncarr
Corey Phone #: ###-####
Final7/25/20177/25/20177/25/2017PFAIL
DetailsMark Moncarr
corey Phone #: ###-#### All areas in question are considered Category 3 Basic Care Space. Category 1 does not require GFI protection. 517.21 states this. All other Category classifications require GFI protection as per 517.21 commentary that reverts to 210.8(B), GFI protection for personnel.
Electrical Rough-In6/27/20176/28/20176/28/2017APASS
DetailsMark Moncarr
Cory Phone #: ###-#### Ok cover front half of re-model. All existing wiring demo, and new MC installed including redundant where needed.
Final5/26/20175/26/20175/26/2017PPART
DetailsMark Moncarr
partial final Phone #: ###-#### Ok PARTIAL final. Waiting for small DW for new side. Wires are safed off.
Conference3/27/20173/28/20173/28/2017APASS
DetailsMark Moncarr
Corey Phone #: ###-#### Supposed to a RI cover. Ok cover