Final | 8/10/2017 | 8/11/2017 | 8/11/2017 | P | PASS |
James Ady
|
|
|
Von is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen final ok
|
Final | 8/1/2017 | 8/2/2017 | 8/2/2017 | P | CANC |
James Ady
|
|
|
Von is the onsite contact. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Sean DeLacy
|
Final | 6/22/2017 | 6/23/2017 | 6/23/2017 | A | PART |
James Ady
|
|
|
Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Will need to come back to check cubicles temp final ok
|
Final | 6/20/2017 | 6/21/2017 | 6/21/2017 | P | FAIL |
James Ady
|
|
|
Von is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Wrong contact number. 210.8 B 5 All receps within 6ft of sink shall be GFCI protected. (To right of sink along wall in small breakroom) 406.6 Receptacle face plates shall be installed. (All conference room NET panels) Cubicles shall be installed to verify power in whips provided.
|
Electrical Rough-In | 5/4/2017 | 5/5/2017 | 5/5/2017 | P | PASS |
Eric Story
|
|
|
Ceiling Cover Phone #: ###-#### Inspection requested via web by Buster Bowen Ceiliings only ok cover
|
Electrical Rough-In | 4/25/2017 | 4/26/2017 | 4/26/2017 | A | PASS |
James Ady
|
|
|
Wall Cover.. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Conference room 1 and 2 Walls only Rough in ok
|
Electrical Rough-In | 4/14/2017 | 4/17/2017 | 4/17/2017 | P | PASS |
James Ady
|
|
|
Wall Rough. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen walls only ok to cover
|