Final | 6/30/2017 | 6/30/2017 | 6/30/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn final ok
|
Rough-In Permanent Service | 4/17/2017 | 4/17/2017 | 4/17/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Can openings in soffits do not have fire protection at time of inspection. Rest on corrections complete. Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 4/14/2017 | 4/17/2017 | 4/17/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Wui Zone A soffit cans not covered.
210.52(I)- Foyers over 60 sq.ft shall have a receptacle outlet installed on all walls 3' and wider. 210.70(A)(2)(b)- All exterior doors shall have an opening for illumination. Can in place wiring. 334.12- NM cable shall not be installed where subject to physical damage. Master hall hanging below ceiling. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" they shall be protected by nail plates. Garage east wall (3), m. shower 45 degree, m vanity 45 degree and above and secure below GFI center staple or protect.
|