Permit Information
Permit NumberELE17-01032
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 1825 W BEACON ST
Project Name 
Customer Number3709
ePlanReviewNo
Description
New: Complete Electrical Installation for ground up construction. New underground conduit, wiring, boxes, cable tray, lights and fixtures, receptacles, panels and telecomm.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/30/20185/31/20185/31/2018APASS
DetailsEric Story
Lower Level inspection all areas
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Tom Betty
Final occ card signed, Final ok
Final5/29/20185/30/20185/30/2018PPART
DetailsEric Story
Lower Level all areas final inspection.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Tom Betty
Temp occ card signed waitng for main final for 5/31/18 if all plates and panic hard ware installed
Conference5/9/20185/9/20185/9/2018ADONE
DetailsEric Story
Installation of a fireplace outside. Phone #: ###-#### Inspection requested via web by Scott Wilson
Discussed GFCI protection of fire place on patio with cord and plug type.
Final5/7/20185/7/20185/7/2018APART
DetailsEric Story
Finals in Units:
100, 101, 102, 103, 104, 105, 106
200, 201, 202, 203, 204, 205, 206 Phone #: ###-#### Inspection requested via web by Scott Wilson
All remaining units checked out fine
Final5/4/20185/4/20185/4/2018APART
DetailsEric Story
Unit finals in 300, 301, 302, 303, 304, 305, 306
401, 402, 403, 404, 405, 406
All of the corridors on 3rd and 4th floors Phone #: ###-#### Inspection requested via web by Scott Wilson
Units as requested ok and corridors as well
Final5/1/20185/2/20185/2/2018ACANC
DetailsEric Story
Trash Room (ground level)
Electrical/ Riser Room dividing wall
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Needed r/i
Electrical Rough-In5/2/20185/2/20185/2/2018PPASS
DetailsEric Story
Trash Room (ground level)
Electrical/ Riser Room dividing wall
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
TRash room and demising wall plus u/g for gate ok to cover
Final4/27/20184/27/20184/27/2018PPART
DetailsEric Story
Final for Roofs
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Roof top units installation ok
Final4/26/20184/26/20184/26/2018APART
DetailsEric Story
Unit finals for 420, 423, 425, 432
and
Rough in for cover Lobby Fireplace
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as requested all checked out fine and are ok
Final4/25/20184/25/20184/25/2018PPART
DetailsEric Story
Unit finals in 320, 322, 323, 324, 325, 326, 328, 330, 332
Janitor closets 206, 306, 406
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as requested checked out fine and are ok
Final4/24/20184/24/20184/24/2018APART
DetailsEric Story
Unit finals in 220,222, 223, 224, 225, 226, 228, 230, 232. Comm Rm. 207, Janitor Rm. 206 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms as noted checked out and are ok
Final4/23/20184/23/20184/23/2018PPART
DetailsEric Story
Unit finals in 120, 122, 123, 124, 125, 126, 128, 130 and 132
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as requested ok
Final4/19/20184/19/20184/19/2018PPART
DetailsJames Ady
1st floor corridor, Rm. 106, 107, 108 and 2nd floor corridor, Rm. 207, 208
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 1st floor corridor Storage rm 106, com rm 107 Trash rm 108, 2nd floor corridor, com rm 207 trash rm 208. Final ok
Final4/18/20184/18/20184/18/2018ANH
DetailsRock A. Hudson
Final for Units 120, 122, 123, 124, 125, 126, 128, 130, 132
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Called contact, no answer, left message to recall when someone is available
Electrical Rough-In3/30/20183/30/20183/30/2018PPASS
DetailsEric Story
Ceiling rough in for cover on ground level Interior space.
Heat trace in garage.
Contact Scott Wilson
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Ok to cover areas as noted on print and heat trace in east side
Final3/26/20183/27/20183/27/2018APART
DetailsEric Story
Finals for Units 107, 110, 207, 210, 307, 310, 407, 410 (Unit Appliance)
Ceiling rough in for cover in garage soffit, Fitness, Lounge, (1/2) corridor, public bathrooms, Quiet Rooms, Janitor closet and hallway.
Contact Scott Wilson.
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as noted on print checked out fine
Electrical Rough-In3/27/20183/27/20183/27/2018PPASS
DetailsEric Story
Finals for Units 107, 110, 207, 210, 307, 310, 407, 410 (Unit Appliance)
Ceiling rough in for cover in garage soffit, Fitness, Lounge, (1/2) corridor, public bathrooms, Quiet Rooms, Janitor closet and hallway.
Contact Scott Wilson.
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print ok to cover ceilings
Final3/21/20183/22/20183/22/2018APART
DetailsEric Story
Units 116, 118, 216, 218, 316, 318, 416, 418
Heat trace in garage area.
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms marked on print checked out fine and are ok
Electrical Rough-In3/22/20183/22/20183/22/2018PPASS
DetailsEric Story
4th Floor Comm. Rm. rough in for cover. Phone #: ###-#### Inspection requested via web by Scott Wilson
4th Floor as noted on print ok to cover walls and ceilings
Final3/20/20183/20/20183/20/2018APART
DetailsEric Story
Final for Units 308, 309, 311, 312, 314, 408, 409, 411, 412, 414
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as marked on print checked out fine
Final3/19/20183/19/20183/19/2018PPART
DetailsEric Story
Units 208, 209, 211, 212, 214
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print units checked out fine
Final3/16/20183/16/20183/16/2018PPASS
DetailsEric Story
Finals for Units 108, 109, 111, 112,114
Partial rough in ceiling inspection for cover in garage. Phone #: ###-#### Inspection requested via web by Scott Wilson
Areas as noted on print ok to cover and rooms as noted all checked out and mark on print.
Final3/16/20183/16/20183/16/2018PFAIL
DetailsEric Story
Finals for Units 108, 109, 111, 112,114
Partial rough in ceiling inspection for cover in garage. Phone #: ###-#### Inspection requested via web by Scott Wilson
Appliance company is installing cords on ranges and dryers Gave a warning to GC and company about not doing this any more
Electrical Rough-In3/6/20183/7/20183/7/2018APASS
DetailsEric Story
Walls only in Lounge and Fitness areas for cover
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Walls in fitness as noted on printed ok to cover
Electrical Rough-In3/1/20183/2/20183/2/2018PPASS
DetailsEric Story
Rough in for cover in 4th floor corridors
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Corridor as marked on print ok to cover
Electrical Rough-In2/28/20182/28/20182/28/2018APASS
DetailsEric Story
1st, 2nd, 3rd corridor and South Electrical, Riser Rooms for cover.
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Corridors riser room walls ok to cover
Electrical Rough-In2/26/20182/27/20182/27/2018APASS
DetailsEric Story
Rough In for Cover
Ground level area from the stairs to the east part of the building.
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Area as noted on print walls only in ground floor ok to cover
Electrical Rough-In2/23/20182/23/20182/23/2018PPASS
DetailsEric Story
Units 100, 101, 102, 103, 104, 105, 106 soffits for cover
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Hard lids as noted on print ok to cover
Electrical Rough-In2/20/20182/20/20182/20/2018PPASS
DetailsJames Ady
Rough in Units 200, 201, 202, 203, 204, 205, 206, 300 soffits for cover
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Soffits only ok to cover
Electrical Rough-In2/19/20182/20/20182/20/2018ACANC
DetailsEric Story
Rough-In Units 100, 101, 102, 103, 104, 105, 106 soffits for cover
Contact Scott Wilson
Thank you, Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
Electrical Rough-In2/15/20182/15/20182/15/2018APASS
DetailsEric Story
Rough-In for Cover
Units 301, 302, 303, 304, 305, 306 soffits
Area 2 and 3 corridor ceilings on floors 1-3
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units and corridors as marked on print for hard lids ok to cover
Permanent Service2/14/20182/14/20182/14/2018PPASS
DetailsEric Story
Main gear and branch panels
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
p/s u/g n ok
Emails saved for availiable fault calc 25,009 amp max in rush from IPCO and breaker is 65K rated
Electrical Rough-In2/12/20182/13/20182/13/2018PPASS
DetailsEric Story
Inspection for cover:
Fire Smoke dampers in the northwest corner on floors 1, 2, 3
Unit 401, 402, 403, 404, 405, 406 soffits
Wall in front of elevator on 4th floor
Contact Scott Wilson
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print ok to cover
Electrical Rough-In2/8/20182/8/20182/8/2018PPASS
DetailsEric Story
Rough-In for cover Units 420, 423, 425, 432 soffits.
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print ok to cover
Electrical Rough-In2/7/20182/7/20182/7/2018PPASS
DetailsEric Story
Inspection for cover:
Janitors Closets on floors 1-4, 4th floor corridor, Unit 402 east wall, Unit 320 soffits, 1st floor fire damper Phone #: ###-#### Inspection requested via web by Scott Wilson
Areas as noted on print ok to cover.
Talked about lockable disc for dampers in hallways as per 110.25
Electrical Rough-In2/1/20182/1/20182/1/2018PPASS
DetailsEric Story
Inspection for cover in Units 232, 322, 323, 324, 325, 326, 328, 330, 332 Soffits and the North Stairs.
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print hard lids and north stair ok to cover
Electrical Rough-In2/1/20182/1/20182/1/2018PCANC
DetailsEric Story
Inspection for cover in
Units 232, 322, 323, 324, 325, 326, 328, 330, 332 Soffits
Contact Scott Wilson
Thank you Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
Electrical Rough-In1/29/20181/29/20181/29/2018PPASS
DetailsEric Story
Units 130 and 132 soffits for cover inspection.
Elevator consultation also.
Contact Scott Wilson
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as descibed ok to cover hardd lids
Electrical Rough-In1/25/20181/25/20181/25/2018PPASS
DetailsEric Story
Units 216, 218, 220, 222, 223, 224, 225, 226, 228, 230 soffits for cover.
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as noted on print ok to cover hard lids
Electrical Rough-In1/23/20181/24/20181/24/2018APASS
DetailsEric Story
Units 123, 124, 125, 126,128 soffits and 1st floor corridor 105
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print and inspection request ok to cover
Electrical Rough-In1/19/20181/19/20181/19/2018APASS
DetailsEric Story
Units 302, 303, 304, 305, 306, 402, 403, 404, 405, 406 for cover
Unit 122 soffit for cover
Contact Scott Wilson
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as noted on print walls and hard lids ok to cover
Electrical Rough-In1/18/20181/18/20181/18/2018PPASS
DetailsEric Story
Rough-In for cover for Units 116, 118 and 120 soffits
Contact Scott Wilson
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as requested and marked on print ok to cover drop ceilings
Electrical Rough-In1/10/20181/10/20181/10/2018PPASS
DetailsEric Story
Rough-in for cover:
2nd (205) and 3rd (305) floor corridor walls in area 1
4th (402) floor corridor in area 2
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Corridors as marked on print ok to cover walls only
Electrical Rough-In1/9/20181/9/20181/9/2018PPASS
DetailsEric Story
Inspection for cover in:
Units: 102, 103, 104, 105, 106, 202, 203, 204, 205, 206
Soffits: Units 407, 408, 409, 410, 411, 412, 414, 416, 418
Contact Scott Wilson
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms as noted on print ok to cover
Electrical Rough-In1/3/20181/4/20181/4/2018APASS
DetailsEric Story
Inspection for cover
Units 100, 200, 101, 201, 203, 204, 132, 232, 332, 432.
Contact Scott Wilson.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units as noted on print and inspection request ok to cover
Electrical Rough-In12/28/201712/28/201712/28/2017APASS
DetailsEric Story
3rd floor soffits in units - 307, 308, 309, 310, 311, 312, 314, 316, 318 Phone #: ###-#### Inspection requested via web by Scott Wilson
Areas as noted on print drop ceilings ok to cover
Electrical Rough-In12/27/201712/27/201712/27/2017PPASS
DetailsEric Story
Room 333 hard lids and walls only ok to cover
Electrical Rough-In12/19/201712/19/201712/19/2017APASS
DetailsEric Story
Inspection for cover – Units 125, 225, 325, 130, 230, 330
Trash Rooms – Levels 1-4
Mechanical Rooms – Levels 1-3
East (Oakland Rd.) Corridor Levels 1-3
Contact Scott Wilson
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print and inspection request
ok to cover
Electrical Rough-In12/6/201712/6/201712/6/2017PPASS
DetailsEric Story
Rough-in inspection for cover in Units 320, 322, 323, 324, 326, 328, 420, 423
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on inspection request and noted on prints ok to cover
Electrical Rough-In11/30/201712/1/201712/1/2017APASS
DetailsEric Story
Rough-In inspection for cover in Units 207, 208, 209, 210, 211, 212, 214 soffits.
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on print, Hard lids ok to cover
Electrical Rough-In11/27/201711/28/201711/28/2017APASS
DetailsEric Story
Rough-in inspection for Units 120, 122, 123, 124, 126, 128, 220, 222, 223, 224, 226 and 228 for cover. Also needed is an elevator consultation.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on inspection request walls and hard lids only ok to cover.
Discussed location of elevator disc and shunt trip ,advised contractor to call state of ID for approval of locations as he wants to locate panels......
Conference11/22/201711/22/201711/22/2017ADONE
DetailsEric Story
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed M/C feeders ran close to each other,
No derated required for they are in there own raceway...
Electrical Rough-In11/16/201711/17/201711/17/2017APASS
DetailsEric Story
Inspection for Unit 111 and Stairwell #2 (south stairs)
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Unit 111 hard lids in kitchen and baths and stair #2 on south side walls only ok to cover
Electrical Rough-In11/15/201711/16/201711/16/2017APART
DetailsRock A. Hudson
Rough in for Cover
1st floor soffit in Units 107, 108, 109, 110, 111, 112, 114.
4th floor corridor, Area 3
Contact Scott Wilson
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
111 not ready, 107 thru 110, 112, 114 drop lids and 4th floor corridor walls only rough in ok cover
Electrical Rough-In11/8/201711/9/201711/9/2017APASS
DetailsEric Story
Rough-In inspection for cover in Area 3; 1st, 2nd and 3rd floor corridors.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
1st floor 2nd floor 3rd floor corridor walls only ok to cover as marked on print.
Discussed wiring of elevator install, will need to get approved plans and location of shunt trip breaker and disc for motors.
Electrical Rough-In11/2/201711/2/201711/2/2017PPASS
DetailsEric Story
Rough-in for cover in units 116, 118, 216, 218, 316, 318, 416 and 418
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units 118,116,216,218,316,318,416,418 hard lids and walls only ok to cover
Electrical Rough-In11/2/201711/2/201711/2/2017PFAIL
DetailsEric Story
Rough-in for cover in units 116, 118, 216, 218, 316, 318, 416 and 418
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed removing of insulation installed proir to inspection will have it removed.
Electrical Rough-In10/23/201710/24/201710/24/2017APASS
DetailsEric Story
Area 3, floors 3 ; 4, rough in for cover
Contact Scott Wilson 208###-####
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units 311,309,310,308,312,314-411,409,407,408,410,412,414 hard lids and walls ok to cover
Electrical Rough-In10/20/201710/20/201710/20/2017PCANC
DetailsEric Story
“3rd floor, Area 3; rough in for cover”, Units 307, 308, 309, 310, 311, 312 and 314
Contact Scott Wilson
Thank you, Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
Electrical Rough-In10/20/201710/20/201710/20/2017ACANC
DetailsEric Story
“3rd floor, Area 3; rough in for cover”, Units 307, 308, 309, 310, 311, 312 and 314
Contact Scott Wilson
Thank you Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
Rough-In Permanent Service10/11/201710/12/201710/12/2017APASS
DetailsDaryl DeGrange
Rough In inspection for Units 107-108-109-110-111-112-114-207-208-209-210-211-212-214. First ; second floor halls.
Contact John McElroy ###-####
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek No service inspection- Rough-in ok cover walls and hard lids
Conference10/4/201710/4/201710/4/2017PDONE
DetailsEric Story
Consult
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Verified windows and was told roofing material is in place to keep moisture from entering building to protect romex cable, ok to proceed pulliong wire on west end of building
Electrical Rough-In9/18/20179/18/20179/18/2017APASS
DetailsEric Story
Ufer ground inspection.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Concrete encased electrode ok to cover
Conference9/12/20179/12/20179/12/2017PDONE
DetailsEric Story
Consult for booster pump location
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed moving of fire pump, told them they would need to get it approved per Fire Marshall/Fire Inspector/ and City of Boise.
Will not make that call if it ok to move pumps around, If all NEC working clearences are in place pump may stay in place....
Electrical Rough-In9/8/20179/8/20179/8/2017PPASS
DetailsEric Story
Underground Phone #: ###-#### Inspection requested via web by Scott Wilson
u/g fo feeders ok to cover
Electrical Rough-In8/24/20178/24/20178/24/2017PPASS
DetailsEric Story
Ground Inspection
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
u/g for lobby ok to cover
Electrical Rough-In8/10/20178/10/20178/10/2017PPASS
DetailsEric Story
Underground inspection for Identity Student Housing.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
u/g for feeders part 2 ok cover
Electrical Rough-In8/8/20178/8/20178/8/2017PPASS
DetailsEric Story
Underground Inspection for Identity Student Housing
Contact Scott Wilson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Phase 1 u/g for feeders in parking garage ok cover
Conference8/1/20178/1/20178/1/2017PPASS
DetailsEric Story
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed layout of receptacles in rooms and wall spacing requirements, will address spacing in ADA rooms with fixed window panels that will not meet 210.52 wall spacing for 12' ......
Conference7/20/20177/20/20177/20/2017ADONE
DetailsEric Story
Consultation at Identity Student Housing.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed using vaults in electrical room for bending radius and conduits, fused and unfused shall not be in same raceway. Also talked about running romex prior to roof being in place, will omly install when 2 floors above have been framed and precaution will be made to insure wire does not get wet, ESI will send a email saying how they will prevent any water damage from saturating wires and if so romex will be replaced as needed....
Electrical Rough-In7/13/20177/13/20177/13/2017APASS
DetailsEric Story
Underground Inspection
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
u/g ok cover
Electrical Rough-In7/6/20177/6/20177/6/2017PPASS
DetailsEric Story
Underground Inspection
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Electrical room under good, plenty of depth for next stage of runs before plumber comes, pictures ok at this time.
Electrical Rough-In6/22/20176/22/20176/22/2017PPASS
DetailsMark Moncarr
Uffer ground inspection on 2nd floor deck.
Contact Scott Wilson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Ok cover ufer. 800.100(A)(3), #6 cu was used for GEC.
Electrical Rough-In5/23/20175/23/20175/23/2017PPASS
DetailsJames Ady
Ufer ground. Starting underground conduit. Phone #: ###-#### Inspection requested via web by Scott Wilson UFER ok, Underground from vault to first stem wall ok to cover
Conference5/8/20175/9/20175/9/2017ACANC
DetailsEric Story
Consultation for Identity Student Housing.
Contact Scott Wilson.
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Scheduled for wrong day
Electrical Rough-In4/11/20174/12/20174/12/2017APART
DetailsEric Story
Uffer ground inspection.
Contact Tom Betty
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Uffer ok cover