DOC - Permit Expired | 3/18/2019 | 3/18/2019 | 3/18/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Electrical Rough-In | 7/19/2017 | 7/20/2017 | 7/20/2017 | A | PASS |
Rock A. Hudson
|
|
|
reinspect Phone #: ###-#### Inspection requested via web by Dave Koeppen Underground changes from PVC to IMC at south end, shall remain metallic to a point it can be bonded. Rough in ok cover
|
Final | 7/19/2017 | 7/20/2017 | 7/19/2017 | A | CANC |
Rock A. Hudson
|
|
|
reinspect for groung Phone #: ###-#### >> Inspection requested via web by Dave Koeppen Inspection cancelled from web by: Dave Koeppen
|
Electrical Rough-In | 7/6/2017 | 7/7/2017 | 7/7/2017 | A | FAIL |
Eric Story
|
|
|
Underground /// justin ###-#### 300.5 must maintain 24" under parking lots
|