Final | 8/2/2017 | 8/3/2017 | 8/3/2017 | A | PASS |
James Ady
|
|
|
Final and inspect uffer concrete Phone #: ###-#### Inspection requested via web by Emmet Bushman Corrections made final ok
|
Electrical Rough-In | 8/1/2017 | 8/2/2017 | 8/2/2017 | A | PASS |
James Ady
|
|
|
Inspect uffer ground wire prior to concrete pour Phone #: ###-#### Inspection requested via web by Emmet Bushman ufer only ok to cover
|
Final | 7/25/2017 | 7/31/2017 | 7/31/2017 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman 210.8 all exterior receptacles shall have GFCI protection 250.32 seperate structures shall have grounding electrode system installed
|
Final | 7/28/2017 | 7/28/2017 | 7/28/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman 250.32- Building fed with feeders or branch circuits shall have a grounding electrode system installed. Unable to gain access to house or garage. house has sign stating wet floors no access until 7-29-17 no acceptions and garage has wet concrete at all entrances.
|
Electrical Rough-In | 6/20/2017 | 6/20/2017 | 6/20/2017 | P | PASS |
Eric Story
|
|
|
Floor heat rough in Phone #: ###-#### Inspection requested via web by Emmet Bushman Master bath floor heat ok cover
|
Permanent Service | 5/31/2017 | 6/1/2017 | 6/1/2017 | A | DONE |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman Already had perm serv inspection
|
Electrical Rough-In | 4/26/2017 | 4/27/2017 | 4/27/2017 | P | PASS |
Rock A. Hudson
|
|
|
no service inspection at this time Phone #: ###-#### Inspection requested via web by Emmet Bushman Service located on east side of garage and subfeeds house. 250.32 buildings fed by feeders or branch circuits shall have a grounding electrode system installed. Unable to locate a concrete encased electrode at house, ground rods must be installed when energized. Feeders not in at time of inspection and conduit needs relocated. Rough in ok cover
|
Permanent Service | 4/27/2017 | 4/27/2017 | 4/27/2017 | P | PASS |
Rock A. Hudson
|
|
|
no service inspection at this time Phone #: ###-#### Inspection requested via web by Emmet Bushman Service installed at time of inspection however underground must be relocated. p/s u/g n ok
|