Final | 5/6/2019 | 5/9/2019 | 5/9/2019 | A | PASS |
James Ady
|
|
|
9 am if possible Phone #: ###-#### Inspection requested via web by Christophe Keys Corrections made Final ok
|
Final | 4/26/2019 | 4/30/2019 | 4/30/2019 | A | CANC |
Eric Story
|
|
|
Agreed upon time of 9:00 AM Phone #: ###-#### Inspection requested via web by Christophe Keys Duplicate request
|
Final | 4/26/2019 | 4/30/2019 | 4/30/2019 | A | FAIL |
Eric Story
|
|
|
Agreed upon time of 9:00 AM Phone #: ###-#### Inspection requested via web by Christophe Keys 210.8 All receptacles serving counter top shall be GFCI protected 406 All recetpacles shall be tamper proof 314 All boxes recessed in tile shall have a listed type box extender 11.25 Lockable disc for hard wired appliances(dishwasher) Re check all devices for GFCI protection Receptacle for micro is free floating behind micro
|
ELE-Aging Inspection | 4/18/2019 | 4/18/2019 | 4/18/2019 | | DONE |
James Ady
|
|
|
Left message to call for final.
|
Electrical Rough-In | 5/17/2017 | 5/18/2017 | 5/18/2017 | A | PASS |
James Ady
|
|
|
Kitchen rough-in Phone #: ###-#### Inspection requested via web by Christophe Keys Kitchen only ok to cover
|