Final | 8/2/2017 | 8/3/2017 | 8/3/2017 | P | PASS |
Rock A. Hudson
|
|
|
Any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
|
Final | 8/1/2017 | 8/2/2017 | 8/2/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Any questions please call ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller 210.8(B)- All 15 or 20 amp 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Bar both sides. 314.25- All boxes shall have covers. 1 front light and back room 8"x10" junction box. 110.3- Double duplex receptacle not working and open neutral in front areas
|
Electrical Rough-In | 6/1/2017 | 6/2/2017 | 6/1/2017 | A | PASS |
Rock A. Hudson
|
|
|
Cover Phone #: ###-#### Inspection requested via web by Louis Keller Check interior panel for seperation of grounds and neutrals. Most wiring to be surface mounted for industrial look. Walls and hardlid rough in ok cover
|
Electrical Rough-In | 5/31/2017 | 6/1/2017 | 6/1/2017 | A | NH |
Rock A. Hudson
|
|
|
Cover Inspection Phone #: ###-#### Inspection requested via web by Louis Keller Door locked left message with contractor.
|