Final | 8/16/2017 | 8/16/2017 | 8/16/2017 | A | PASS |
Rock A. Hudson
|
|
|
Please call Doug at ###-#### with 15 minutes notice so that he can meet you there. Inspection requested via web by Barbara Szurgot Owners to contact other electrical contractor about open permit. Final ok
|
Final | 8/14/2017 | 8/15/2017 | 8/15/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.3- Corridor receptacle outlet not working. 210.8( B)- All receptacle outlets 120 volt located with in 6' of a sink shall have GFCI protection. Back classroom with new sink. 314.20- Where boxes are mounted more than 1/4" from surface of wall a spark ring shall be installed. Bath outlets and others. 404.10- Corridor bath switch not mounted and wiring tied thru. Only electrician shall do work. Energy code- All areas shall have OCC sensors as noted on print. ELE14-02605 for sancuary and upstairs must also final for that work.
|
Electrical Rough-In | 7/31/2017 | 7/31/2017 | 7/31/2017 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling grid inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot Grid rough in ok cover
|
Electrical Rough-In | 6/6/2017 | 6/6/2017 | 6/6/2017 | P | PASS |
Rock A. Hudson
|
|
|
Doug Phone #: ###-#### 2nd permit exists for sanctuary and upstairs area ELE14-02605. Foyer, family room, offices, and bathrooms walls and hardlids rough in ok cover.
|