Final | 7/17/2017 | 7/21/2017 | 7/21/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew White...
corrections made...ok to final
|
Final | 6/23/2017 | 6/26/2017 | 6/26/2017 | P | NR |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew White...
discussed with contractor what needed to be done to meet code
|
Final | 6/9/2017 | 6/9/2017 | 6/9/2017 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew White....
1) intersystem bond shall be added at service location...770.100
2) breakers shall be installed such that the center of the grip of the operating handle of circuit breaker is not more than 6 ft 7 inches....404.8
|