Final | 8/29/2017 | 8/30/2017 | 8/30/2017 | A | PASS |
Mark Moncarr
|
|
|
garage code should be 9766 Phone #: ###-#### Inspection requested via web by Lynn Cable Ok final
|
Rough-In Permanent Service | 6/1/2017 | 6/2/2017 | 6/2/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Cable Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 5/30/2017 | 6/1/2017 | 6/1/2017 | A | FAIL |
Rock A. Hudson
|
|
|
New Home inspection, contact name is Travis Phone #: ###-#### Inspection requested via web by Lynn Cable 210.11(C)(3)- Required 20 amp 120 volt circuit for bathroom receptacles shall have no other outlets. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates. Up be marked on stud and M closet above switch. 352.6- All PVC fittings shall be listed. 1-piece Cantex expansion joint is not a listed product. Provided by their web site.
|