Final | 6/20/2017 | 6/21/2017 | 6/21/2017 | A | PASS |
Eric Story
|
|
|
Corrections were noted, it is now a 60 amp panel Phone #: ###-#### Inspection requested via web by Steven Meredith Correction fixed final ok
|
Electrical Rough-In | 6/5/2017 | 6/5/2017 | 6/5/2017 | A | PASS |
Rock A. Hudson
|
|
|
Ready for a cover inspection, ground inspection access to be added later! any other questions plz call me! Thx Steve ###-#### Phone #: ###-#### Inspection requested via web by Steven Meredith 110.3- Square D panel shall only have circuit breakers installed listed for this enclosure. 225.39(D)- Branch circuit for garage with 3 branch circuits shall not be less than 60 amps. All can be corrected after wall cover is installed. Garage rough in ok cover
|