Final | 8/2/2017 | 8/2/2017 | 8/2/2017 | P | PASS |
Mark Moncarr
|
|
|
Inspection requested via web by jamie berg No other work has been done. Closing out permit.
|
Permanent Service | 8/1/2017 | 8/2/2017 | 8/2/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g n ok. Corrections needed to be made from previous work done by others. Centerline Elec made all corrections to items listed below. 250.8(5)proper hardware was installed to replace self tapping sheet metal screw used to secure ground lug. 110.14(A) Some strands of conductor feeding house panel were not under terminal. Some strands bent and smashed outside of terminal
|
Permanent Service | 6/21/2017 | 6/21/2017 | 6/21/2017 | P | PASS |
Tom Saunders
|
|
|
200 amp service Phone #: ###-#### Inspection requested via web by jamie berg...
p/s u/g n ok
|