Final | 12/26/2017 | 12/26/2017 | 12/26/2017 | P | PASS |
Eric Story
|
|
|
Harlan Phone #: ###-#### Final ok
|
Electrical Rough-In | 11/14/2017 | 11/15/2017 | 11/15/2017 | A | PASS |
Rock A. Hudson
|
|
|
Harlan Phone #: ###-#### Horizontal runs located at back of garage not covered and shall be covered for final. Rough in ok cover
|
Electrical Rough-In | 11/13/2017 | 11/13/2017 | 11/13/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Harlan Phone #: ###-#### 110.27(A)(4)(a)- Electrical equipment located below 8' from floor shall be protected from physical damage. All wiring located below 8'. 250.148- All equipment grounding conductors located in a box shall be connected together by approved means. 2 gang by man door. 352.30- PVC shall be secured in place with in 3' of a box or conduit body. Secure below house service and garage panel.
|
Electrical Rough-In | 9/11/2017 | 9/11/2017 | 9/11/2017 | P | PASS |
Rock A. Hudson
|
|
|
Harlan Phone #: ###-#### Underground from house to garage rough in ok cover
|
Conference | 8/23/2017 | 8/23/2017 | 8/23/2017 | P | DONE |
Rock A. Hudson
|
|
|
Harlan-please call 15 minutes prior to meet Phone #: ###-#### Discussed wiring for detached garage with unfinished walls and 100amp feed. 1 outdoor light at each man door controlled by switch or automatic means, minimum of 2 receptacles for car bays for depth, all 120 volt receptacle outlets shal be 20 amp, tamper resistant, GFCI protected and wiring shall be protected from physical damage by wiring meathod or framing if MN cable. Minimum of #4 for garage feeders with #6 ground and 2 ground rods at garage. Depth of underground shall be 18" for conduit or 24" for cable.
|