Permit Information
Permit NumberELE17-02155
StatusFinaled
Name ANDERSON & WOOD CONSTRUCTION
Site Address 3033 W ELDER ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Provide electrical connections to new mechanical connections, set new switchgear, add termination cabinet next to Idaho Power transformer.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/24/20184/24/20184/24/2018PPASS
DetailsRock A. Hudson
404.8 ex 2- Disconnect switch for equipment may be above 6'7" if accessible by potable means. Final ok
Final4/17/20184/18/20184/18/2018AFAIL
DetailsRock A. Hudson
We are not currently on site. Please call Frank 30 minutes prior to arrival so he can meet you. Phone #: ###-#### Inspection requested via web by Kelly Tarter Chiller disconnecting means shall be located at a readily accessible location below 6'7". Handle on units shall have a platform built below operable handle so handle location 6'7" or lower.
Conference2/15/20182/15/20182/15/2018PDONE
DetailsEric Story
Frank Phone #: ###-####
Discussed work clearences in Fire riser room, Being there is no serviceable equipment ina VFD and room is only accessible by qualified personal motor that is in front of VFD is ok to be installed inn that location
Electrical Rough-In1/9/20181/10/20181/10/2018APASS
DetailsEric Story
This is an underground inspection that will be a two part dig. We are requesting an inspection a 10:30 a.m. to see what we are doing. We will then backfill and proceed to the next section. Phone #: ###-#### Inspection
via web by Kelly Tarter
U/G from main building ok to cover
Electrical Rough-In7/11/20177/11/20177/11/2017APASS
DetailsEric Story
Tyler is looking to have his grounding looked at before the building slab is poured. Phone #: ###-#### Inspection requested via web by Kelly Tarter
Grounding ring ok cover
Electrical Rough-In7/6/20177/7/20177/7/2017APASS
DetailsEric Story
Please contact Tyler at ###-####.
Unerground inspection on the 5 underslab conduits in the chiller building. Phone #: ###-#### Inspection requested via web by Kelly Tarter
u/g around back ok