Permit Information
Permit NumberELE17-02168
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 3327 E PARSNIP PEAK DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Complete wiring of a single family home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/4/201710/6/201710/6/2017PPASS
DetailsJames Ady
Garage code is 6288 enter Phone #: ###-#### Inspection requested via web by Zane Robertson Access provided in fir down Via vent in master closet Final ok
Electrical Rough-In9/7/20179/7/20179/7/2017PPASS
DetailsRock A. Hudson
Floor heat master bedroom Phone #: ###-#### Inspection requested via web by Zane Robertson
Rough in ok cover
Electrical Rough-In9/6/20179/7/20179/7/2017AFAIL
DetailsRock A. Hudson
Floor heat in master bedroom Phone #: ###-#### Inspection requested via web by Zane Robertson
110.3- Cold lead splice shall be located in floor system and be recessed in floor to avoid damage as per manufacturers instructions.
424.38(B)(4)- Heating cable shall not be installed in a wall.
Rough-In Permanent Service7/10/20177/14/20177/14/2017PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Zane Robertson
WUI zone soffit can fire barriers not done.
Remote hood control wire junction point has exposed conductors that shall be installed in a box or conduit as per 300.3. Access will be provided in fir down to enforce at final.
Interior Rough in ok cover p/s u/g n ok