Final | 12/18/2017 | 12/18/2017 | 12/18/2017 | P | PASS |
James Ady
|
|
|
If locked, receptionist has key Phone #: ###-#### Inspection requested via web by Lars Johnson final ok
|
Electrical Rough-In | 7/12/2017 | 7/13/2017 | 7/13/2017 | P | PASS |
Rock A. Hudson
|
|
|
Code issues corrected. Phone #: ###-#### Inspection requested via web by Lars Johnson Rough in ok cover
|
Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Please see receptionist for access to TI space. Phone #: ###-#### Inspection requested via web by Lars Johnson 300.4- Where MC cable is run thru bored holes that do not maintain 1 1/4" from framing surface it shall be protected from physical damage. 314.23(B)- Boxes shall be rigidly mount in place. Kitchen 330.24- MC bending radius shall not damage cable. Kitchen area.
|