Final | 9/29/2017 | 9/29/2017 | 9/29/2017 | P | PASS |
Tom Saunders
|
|
|
The correction have been taken care of, thx Phone #: ###-#### Inspection requested via web by Stephen Kren...
corrections ok....ok to final
|
Final | 9/28/2017 | 9/29/2017 | 9/29/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Pool incomplete on seperate permit. 210.8- All GFCI devices shall be located in a readily accessible location. Vac over 6'7". 210.52(C)(1)- Pantry counter top shall have a receptacle outlet with in 24" of right wall.
|
Rough-In Permanent Service | 7/25/2017 | 7/25/2017 | 7/25/2017 | P | PASS |
Tom Saunders
|
|
|
The corrections have been fixed, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren...
rough ok to cover p/s u/g n ok stated at rough there will be no wallspace to the right of fireplace...shelving will be installed
|
Rough-In Permanent Service | 7/21/2017 | 7/24/2017 | 7/24/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Seperate BLD for pool exists no ELE yet. 210.52(A)(2)- Area above counter or work space count as wall space. Right of fireplace above flat is wall space needs receptacle outlet. 250.64(D)(1)- Grounding electrode tap shall be outside panel and extend to each disconnecting means. 300.4- Nail plates needed on pool HR upper plate and below 2 gang in nook.
|