Permit Information
Permit NumberELE17-02297
StatusFinaled
Name STEPHENS ELECTRIC INC
Site Address 4351 N EDELWEISS ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: wiring for a new single family dwelling
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/29/20179/29/20179/29/2017PPASS
DetailsTom Saunders
The correction have been taken care of, thx Phone #: ###-#### Inspection requested via web by Stephen Kren...

corrections ok....ok to final
Final9/28/20179/29/20179/29/2017AFAIL
DetailsRock A. Hudson
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
Pool incomplete on seperate permit.
210.8- All GFCI devices shall be located in a readily accessible location. Vac over 6'7".
210.52(C)(1)- Pantry counter top shall have a receptacle outlet with in 24" of right wall.
Rough-In Permanent Service7/25/20177/25/20177/25/2017PPASS
DetailsTom Saunders
The corrections have been fixed, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren...

rough ok to cover
p/s u/g n ok
stated at rough there will be no wallspace to the right of fireplace...shelving will be installed
Rough-In Permanent Service7/21/20177/24/20177/24/2017AFAIL
DetailsRock A. Hudson
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
Seperate BLD for pool exists no ELE yet.
210.52(A)(2)- Area above counter or work space count as wall space. Right of fireplace above flat is wall space needs receptacle outlet.
250.64(D)(1)- Grounding electrode tap shall be outside panel and extend to each disconnecting means.
300.4- Nail plates needed on pool HR upper plate and below 2 gang in nook.