Final | 10/16/2017 | 10/16/2017 | 10/16/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Final ok
|
Final | 10/5/2017 | 10/6/2017 | 10/6/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald No access to garage. Missing all 688 bath fans. Need lamps in all vanity lights.
|
Rough-In Permanent Service | 7/30/2017 | 7/31/2017 | 7/31/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 7/27/2017 | 7/28/2017 | 7/28/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald BCC 4 05 23- It shall be unlawful to conceal electrical wiring prior to inspection. Soffits covered prior with several cans, paddle fan, receptacle. Front and both back patios. 300.4- Nail plates required pantry and under stairs. 334.15(B)- NM cable shall not be install where subject to damage. touching top of fireplace flue. Fee due on single family dwelling under 2500 sq. ft. $135.00- $55.00= $80.00. Need permit for pool OK foam seal only
|