Final | 8/2/2017 | 8/2/2017 | 8/2/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg No other work has been done. Closing out permit.
|
Permanent Service | 8/1/2017 | 8/2/2017 | 8/2/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g n ok. There were items to correct from previous work that was done. Centerline Elec was not the original installer. Centerline Elec did correct all listed NEC violations. 250.8(5) Machined screws needed to be installed to replace wood screw with star washer. 110.14(A) Connection of conductors to terminals feeding house did not have a good connection. Some strands were bent and smashed outside of lug.
|
Permanent Service | 7/28/2017 | 7/31/2017 | 7/31/2017 | P | CANC |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by jamie berg
|