Final | 11/14/2017 | 11/14/2017 | 11/14/2017 | P | PASS |
James Ady
|
|
|
Ron Phone #: ###-#### corrections made final ok
|
Final | 11/13/2017 | 11/13/2017 | 11/13/2017 | P | FAIL |
Eric Story
|
|
|
Ron Phone #: ###-#### 210.12 AFCI protection for all 120 receptales(lights) 210.12 Branch circuit shall have AFCI protection
|
Electrical Rough-In | 9/25/2017 | 9/25/2017 | 9/25/2017 | P | PART |
Eric Story
|
|
|
Ron Phone #: ###-#### Corrections fixed rough-in ok cover
|
Electrical Rough-In | 9/20/2017 | 9/21/2017 | 9/21/2017 | A | FAIL |
James Ady
|
|
|
Ron Phone #: ###-#### NM Cable shall not be secured closer than 1 1/4in of face of stud.( Kitchen Peninsula Wall and Bath 4 gang.) Need Abrasion protection on fire place 14-2. Need wire provisions for Peninsula recep and Dish washer.
|
Permanent Service | 8/3/2017 | 8/4/2017 | 8/4/2017 | P | PASS |
Rock A. Hudson
|
|
|
Ron Phone #: ###-#### KO broke out at lower, back side of panel area. Contractor to repair. p/s o/h rec ok
|
Electrical Rough-In | 8/4/2017 | 8/4/2017 | 8/4/2017 | P | PASS |
Rock A. Hudson
|
|
|
Ron Phone #: ###-#### Underground to accessory dwelling rough in ok cover.
|