Permit Information
Permit NumberELE17-02732
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 101 S CAPITOL BLVD
Project NamePCA
Customer Number654
ePlanReviewNo
Description
Alteration: Electrical for TI
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/26/201712/27/201712/27/2017APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
Final12/21/201712/21/201712/21/2017PFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 314.25- Furniture outlets and covers shall be install. If outlets are not being used on furniture blanks shall be installed due to live spade connectors exposed. 314.29- Access shall be provided for electrical boxes. HVAC equipment above grid blocks access panel for existing elevator shaft acess which has electrical located in it. Minimum of 90 degrees for door swing shall be provided
Final12/14/201712/18/201712/18/2017PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
210.8(B)- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Mother's room.
314.25- Furniture outlets and covers shall be install. If outlets are not being used on furniture blanks shall be installed due to live spade connectors exposed.
See RI for IT room ceiling violations.
Electrical Rough-In12/14/201712/18/201712/18/2017AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
314.29- Access shall be provided for electrical boxes. HVAC equipment above grid blocks access panel for existing elevator shaft acess which has electrical located in it. Minimum of 90 degrees for door swing shall be provided.
400.12- Flexible cords shall not be run above or pass thru grid. Receptacle has been relocated however pump has not which has flexible cord.
Electrical Rough-In12/5/201712/6/201712/6/2017AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Inspection request was for IT room grid. 314.29- HVAC unit located above grid in IT room blocksan existing access door to elevator shaft that has electrical boxes. HVAC unit shall be located so access door can be opened 90 degrees for access.
400.12- Flexible cords shall not be installed above grid. Sump pump power cord shall not pass thru or be installed above grid.
Electrical Rough-In12/1/201712/4/201712/4/2017PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
All grid except IT room rough in ok cover
Electrical Rough-In11/28/201711/29/201711/29/2017PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
All grid except IT room and east side as noted on contractor print rough in ok cover
Electrical Rough-In11/27/201711/27/201711/27/2017PPASS
DetailsRock A. Hudson
As early as possible please. Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Boarders ok to install in offices and common areas except IT room 804. Grid rough in for south west area only as noted on contractor print. 3 warnings have been given for covering any areas prior to inspection, future issues will result in complete removal of areas covered in question.
Electrical Rough-In11/21/201711/22/201711/22/2017AFAIL
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Exterior borders, too many MC whips with exposed conductors and open j-boxes above border areas.
Electrical Rough-In9/21/20179/22/20179/22/2017APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Floor 8 entire floor. Wall rough in ok cover