Final | 12/26/2017 | 12/27/2017 | 12/27/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
Final | 12/21/2017 | 12/21/2017 | 12/21/2017 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 314.25- Furniture outlets and covers shall be install. If outlets are not being used on furniture blanks shall be installed due to live spade connectors exposed. 314.29- Access shall be provided for electrical boxes. HVAC equipment above grid blocks access panel for existing elevator shaft acess which has electrical located in it. Minimum of 90 degrees for door swing shall be provided
|
Final | 12/14/2017 | 12/18/2017 | 12/18/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 210.8(B)- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Mother's room. 314.25- Furniture outlets and covers shall be install. If outlets are not being used on furniture blanks shall be installed due to live spade connectors exposed. See RI for IT room ceiling violations.
|
Electrical Rough-In | 12/14/2017 | 12/18/2017 | 12/18/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 314.29- Access shall be provided for electrical boxes. HVAC equipment above grid blocks access panel for existing elevator shaft acess which has electrical located in it. Minimum of 90 degrees for door swing shall be provided. 400.12- Flexible cords shall not be run above or pass thru grid. Receptacle has been relocated however pump has not which has flexible cord.
|
Electrical Rough-In | 12/5/2017 | 12/6/2017 | 12/6/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Inspection request was for IT room grid. 314.29- HVAC unit located above grid in IT room blocksan existing access door to elevator shaft that has electrical boxes. HVAC unit shall be located so access door can be opened 90 degrees for access. 400.12- Flexible cords shall not be installed above grid. Sump pump power cord shall not pass thru or be installed above grid.
|
Electrical Rough-In | 12/1/2017 | 12/4/2017 | 12/4/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton All grid except IT room rough in ok cover
|
Electrical Rough-In | 11/28/2017 | 11/29/2017 | 11/29/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton All grid except IT room and east side as noted on contractor print rough in ok cover
|
Electrical Rough-In | 11/27/2017 | 11/27/2017 | 11/27/2017 | P | PASS |
Rock A. Hudson
|
|
|
As early as possible please. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Boarders ok to install in offices and common areas except IT room 804. Grid rough in for south west area only as noted on contractor print. 3 warnings have been given for covering any areas prior to inspection, future issues will result in complete removal of areas covered in question.
|
Electrical Rough-In | 11/21/2017 | 11/22/2017 | 11/22/2017 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Exterior borders, too many MC whips with exposed conductors and open j-boxes above border areas.
|
Electrical Rough-In | 9/21/2017 | 9/22/2017 | 9/22/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Floor 8 entire floor. Wall rough in ok cover
|