ELE-Aging Inspection | 11/27/2019 | 11/27/2019 | 11/27/2019 | | DONE |
Daryl DeGrange
|
|
|
see final
|
Final | 11/27/2019 | 11/27/2019 | 11/27/2019 | P | PASS |
Daryl DeGrange
|
|
|
job complete, Final ok
|
ELE-Aging Inspection | 8/19/2019 | 8/19/2019 | 8/19/2019 | | PASS |
Daryl DeGrange
|
|
|
job complete, Final ok
|
Final | 9/28/2017 | 9/29/2017 | 9/29/2017 | A | FAIL |
Eric Story
|
|
|
Please call prior. Unit needs to be unlocked. Contact: Javier ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates Idaho power has not energized service at this time, re-inspect fee if not complete on next trip
|
Final | 9/7/2017 | 9/7/2017 | 9/7/2017 | P | CANC |
Eric Story
|
|
|
Contact is Mike his cell ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Needed p/s
|
Permanent Service | 9/7/2017 | 9/7/2017 | 9/7/2017 | P | PASS |
Eric Story
|
|
|
Contact is Mike his cell ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates p/s o/h n ok
|
Final | 9/4/2017 | 9/5/2017 | 9/5/2017 | A | FAIL |
Eric Story
|
|
|
Jake is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 230..28(b) point of attachment shall not be of a coupling
|
Permanent Service | 8/25/2017 | 8/25/2017 | 8/25/2017 | P | FAIL |
Eric Story
|
|
|
Jake is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates 110.24 Avaliable fault current calc required
|