Final | 12/28/2017 | 12/29/2017 | 12/29/2017 | A | PASS |
Daryl DeGrange
|
|
|
Key code is 7600 Phone #: ###-#### Inspection requested via web by Jerry Moore no Cof O card on site, corrections completed final ok
|
Final | 12/20/2017 | 12/20/2017 | 12/20/2017 | A | FAIL |
Tom Saunders
|
|
|
Key Code - 7600 Phone #: ###-#### Inspection requested via web by Jerry Moore... 1) GFI will not set in exam room...110.7 2) outlets with no power in exam rm...110.7 3) open junction box...110.7, 314.28(C) 4) baried junction box behind cabinet...junction boxes shall be accessible...314.29
|
Permanent Service | 10/10/2017 | 10/10/2017 | 10/10/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Jerry Moore...p/s u/g n ok
|
Electrical Rough-In | 9/26/2017 | 9/27/2017 | 9/27/2017 | P | PASS |
Tom Saunders
|
|
|
key box code 7600 Phone #: ###-#### Inspection requested via web by Jerry Moore...
rough complete...ok to cover
|
Rough-In Permanent Service | 9/25/2017 | 9/26/2017 | 9/26/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Lock box code - 7600 Phone #: ###-#### Inspection requested via web by Jerry Moore 110.24- Available fault current for services other than residential shall be posted prior to permanent service inspection. 250.68(A)- Connection to concrete encased electrode shall be accessible. 330.12- MC sub-feed strapped to outer sheeting at back of service. MC shall not be installed where subject to damage as per 300.4. 300.4- Where MC is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage.
|