Final | 12/28/2017 | 12/28/2017 | 12/28/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder Ok final. Corrections made.
|
Final | 12/21/2017 | 12/22/2017 | 12/22/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder 210.52A2 Wall spaces greater than2ft shall hve recep. (master bed under 3 gang). 210.51D At least 1 recep shall be installed within 36in of sink basin. Recep shall be on adjacent wall. ( Master vanity) Exposed romex on either side of fireplace needs safed off, put in j-boxes.
|
Electrical Rough-In | 8/30/2017 | 8/31/2017 | 8/31/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder Dining, Kitchen, loft, Bath and Mud room only. Corrections made ok to cover
|
Electrical Rough-In | 8/25/2017 | 8/25/2017 | 8/25/2017 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder 210.52B2 Nook and dining shall be part of the 2 or more small appliance circuits. 210.52A2 Wall space, Loft, Shall have recep within 6ft of hand rail
|