Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE17-02895
StatusFinaled
Name BOISE BASIN ELECTRIC
Site Address 11470 W EDNA ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/10/20184/10/20184/10/2018PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Alan Lusk Ok final. Corrections made.
Final4/9/20184/10/20184/10/2018AFAIL
DetailsRock A. Hudson
Garage code 1155E Phone #: ###-#### Inspection requested via web by Alan Lusk
110.14- Disimilar metals shall not come in contact. West AC splice copper and aluminum wire nutted together.
210.8- Receptacle outlets located with in 6' of a sink shall have GFCI protection. 120 volt dryer receptacle.
Rough-In Permanent Service8/31/20178/31/20178/31/2017PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Alan Lusk...

rough ok to cover
p/s o/h n ok