Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE17-03005
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1140 S COLORADO AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Evaluation & consultation for future project
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/13/20195/17/20195/16/2019APASS
DetailsJames Ady
Contact: Paul Wheeler.... old permit for consultation, need to final and close Phone #: ###-#### Inspection requested via web by Deb Gooden All items in conference have been addressed. Final ok
Final3/20/20193/20/20193/20/2019PCANC
DetailsJames Ady
Contact: Paul Wheeler Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
Conference9/11/20179/12/20179/12/2017ADONE
DetailsJames Ady
Contact: Brian Gee.. Would like to schedule for 9:00 or 11:00, please call before going Phone #: ###-#### Inspection requested via web by Deb Gooden Met onsite Discussed article 110.26 B. Electrical working space shall not be used for storage. 110.26 C 2. @ Egress paths for services over 1200Amps. 110.26 C 3. Panic hardware on egress doors on services over 800A. 110.26 D. Lighting for service rooms.210.64. Service Receptacle Required. Also discussed removing old exposed romex and "cleaning" up unsafe wiring.