Permit Information
Permit NumberELE17-03007
StatusFinaled
Name LARRYS ELECTRIC
Site Address 4905 N MOUNTAIN VIEW DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Electrical for new accessory dwelling
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/27/201712/28/201712/28/2017APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Larry Richardson
Correction fixed final ok
Final12/23/201712/26/201712/26/2017AFAIL
DetailsEric Story
Re- inspect electrical final Phone #: ###-#### Inspection requested via web by Larry Richardson
110 As per manufacturer specs 2pole 100 amp breaker is located in a spot that is rated 50 amp max
Final12/21/201712/22/201712/22/2017AFAIL
DetailsTom Saunders
Inspection requested via web by Larry Richardson...
1) lift pump outlet shall be gfi protected
2) breaker lock out needs installed on dishwasher circuit
3) breaker lockout needs installed on water heater circuit
4) w/p outlet shall have a in use heavy duty cover
5) service outlet is needed within 25' of back hvac unit
Electrical Rough-In11/7/201711/8/201711/8/2017APASS
DetailsTom Saunders
Larry Phone #: ###-####...rough ok to cover
Electrical Rough-In9/11/20179/12/20179/12/2017APASS
DetailsEric Story
Inspect underground conduit to building Phone #: ###-#### Inspection requested via web by Larry Richardson
u/g from pool panel to detached building ok cover(sharpy notes on conduit says under concrete, only had 4" of depth)