Final | 12/27/2017 | 12/28/2017 | 12/28/2017 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Larry Richardson Correction fixed final ok
|
Final | 12/23/2017 | 12/26/2017 | 12/26/2017 | A | FAIL |
Eric Story
|
|
|
Re- inspect electrical final Phone #: ###-#### Inspection requested via web by Larry Richardson 110 As per manufacturer specs 2pole 100 amp breaker is located in a spot that is rated 50 amp max
|
Final | 12/21/2017 | 12/22/2017 | 12/22/2017 | A | FAIL |
Tom Saunders
|
|
|
Inspection requested via web by Larry Richardson... 1) lift pump outlet shall be gfi protected 2) breaker lock out needs installed on dishwasher circuit 3) breaker lockout needs installed on water heater circuit 4) w/p outlet shall have a in use heavy duty cover 5) service outlet is needed within 25' of back hvac unit
|
Electrical Rough-In | 11/7/2017 | 11/8/2017 | 11/8/2017 | A | PASS |
Tom Saunders
|
|
|
Larry Phone #: ###-####...rough ok to cover
|
Electrical Rough-In | 9/11/2017 | 9/12/2017 | 9/12/2017 | A | PASS |
Eric Story
|
|
|
Inspect underground conduit to building Phone #: ###-#### Inspection requested via web by Larry Richardson u/g from pool panel to detached building ok cover(sharpy notes on conduit says under concrete, only had 4" of depth)
|