Permit Information
Permit NumberELE17-03066
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 110 N 11TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: electrical remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/27/201711/27/201711/27/2017PPASS
DetailsEric Story
we are requesting a final inspection on this project.
our person of contact is Bryant ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate
Final ok Card signed on site
Final11/20/201711/21/201711/21/2017AFAIL
DetailsRock A. Hudson
We are requesting a final inspection for tomorrow morning. Our contact is Bryant at ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
210.8(B)- All receptacle outlets located in kitchens shall have GFCI protection. Panini press 20 amp 208 volt receptacle.
314.25- All boxes shall have covers. Bath vanities, south room,
Final11/20/201711/21/201711/20/2017PCANC
DetailsRock A. Hudson
We are requesting a final inspection. Bryant is our contact ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
Final11/17/201711/20/201711/20/2017PCANC
DetailsRock A. Hudson
We are requesting a final inspection for this project please. Our contact is
Bryant ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
Electrical Rough-In11/14/201711/15/201711/15/2017APASS
DetailsRock A. Hudson
We are requesting a above ceiling inspection for tomorrow morning. Our contact is Bryant @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate
Kitchen grid rough in ok cover
Electrical Rough-In9/28/20179/29/20179/29/2017PPASS
DetailsRock A. Hudson
We are requesting a rough wall inspection for the kitchen area. Byrant, is our P.O.C. ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed new GFCI requirements. Kitchen and bar walls rough in ok cover.
Electrical Rough-In9/21/20179/22/20179/22/2017APASS
DetailsRock A. Hudson
We are requesting a rough-in inspection for the dining room light and ceiling for tomorrow morning. Our contact is Tony @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Pendants are about 2 lbs each and flourescents supported. Rough in ok cover
Electrical Rough-In9/14/20179/15/20179/15/2017PFAIL
DetailsRock A. Hudson
We are requesting a rough-in inspection for the dining room lights and a cover inspection in the dining room as well. Our contact is Tony @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate
410.36(B)- Grid shall be used as sole support of luminaires. Luminaires shall be supported indepndant of grid.
300.15- All wiring terminations shall be contained in a box. Old flourescents located above grid have open wiring visible.