Final | 1/24/2018 | 1/25/2018 | 1/25/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by William Andrews corrections made final ok
|
Final | 1/10/2018 | 1/12/2018 | 1/12/2018 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by William Andrews Battery terminals shall be protected as per 110.27. DC array wires shall be protected from physical damage and raceway labeled as per 690.31G3. Disc on house shall be bonded as per 250.148 Panel in basement shall be labeled as per 408.4. Replace 50A backfed breaked with 30A
|
Conference | 9/25/2017 | 9/26/2017 | 9/26/2017 | A | DONE |
James Ady
|
|
|
Please call about 30 min ahead Phone #: ###-#### Inspection requested via web by William Andrews DIscussed Labeling of disc( line and load Energized) Bonding of array, Need to protect batteries as per 110.26. Need for building permit,
|