Final | 1/17/2018 | 1/17/2018 | 1/17/2018 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat Ok final.
|
Electrical Rough-In | 10/26/2017 | 10/27/2017 | 10/27/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat Ok cover. Corrections made.
|
Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Lock Box Code 1811 Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.52- Receptacle outlets shall be installed so that no point measured along floor line is more than 6' from a receptacle outlet. Small front room 1 needed with in 6' of door and front bed window wall. 300.4(E)- Cable shall not be installed above fir strips for roof. front bed 14-2 above rafters, potential damage from roofing.
|
Permanent Service | 10/2/2017 | 10/4/2017 | 10/4/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat p/s o/h rec ok
|