Final | 1/3/2018 | 1/4/2018 | 1/4/2018 | A | PASS |
Mark Moncarr
|
|
|
Kevin Phone #: ###-#### Ok final. All metal fence posts within 5ft bonded. Lights and cover functioned properly while tripping GFI. Was on the phone with Kevin to find out how to turn on pool lights. I had to go into SERVICE mode. Kevin said to put it back in AUTO mode before I left. Pool panel was back in AUTO mode upon leaving.
|
Electrical Rough-In | 12/1/2017 | 12/1/2017 | 12/1/2017 | P | PASS |
Eric Story
|
|
|
equal potencial // Kevin Phone #: ###-#### equipotential bond around perimeter of pool ok to cover
|
Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | PASS |
Mark Moncarr
|
|
|
ug conduit Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Ok cover conduit at depth atleast 20"
|
Electrical Rough-In | 9/26/2017 | 9/26/2017 | 9/26/2017 | P | PASS |
Eric Story
|
|
|
pool bonding Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 4 corners of pool ok to cover
|