Permit Information
Permit NumberELE17-03252
StatusFinaled
Name SOLAR CASCADE
Site Address 3176 E HEARTLEAF CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: we did electrical trim only
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/1/201710/2/201710/2/2017PPASS
DetailsJames Ady
call ron with any questions or concerns ###-#### Phone #: ###-#### Inspection requested via web by Dave Brueggemann Corrections made final ok
Final9/28/20179/28/20179/28/2017PFAIL
DetailsRock A. Hudson
We did the electrical trim only. This house was originally roughed in by another company. Please call Ron at ###-#### for any questions. House should still be open but access code is 5239 key box on west side of garage. If you can reach Ron, Call Jerry at ###-#### Thank you. Phone #: ###-#### Inspection requested via web by Dave Brueggemann
110.3- Equipment shall be wired as per manufacturers instructions. Reverse polarity under stairs, open ground in master closet, patio receptacle not working.
200.6- When using white conductor for ungrounded conductor it shall be identified other than white. Vac circuit.
210.52(C)(3)- Receptacle outlet required at end of peninsula bar.
314.20- Where boxes mounted in tile recessed 1/4" or more extension rings shall be installed.
314.25- All boxes canopies and covers shall completely cover opening. Recessed luminaires shall completely cover box openings. soffits and interior.
334.12- NM cable shall not be installed where subject to physical damage. Garage ladder opening at top.
406.6- Several device covers not installed. Utility, stair, vac opening, disposal.
406.9 and 12- Outdoor receptacle outlets shall be tamper resistant and weather resistant.
422.33- Cord and plug connected jetted tub. Receptacle for tub shall be accessible. Unable to see or test.