Final | 6/14/2018 | 6/15/2018 | 6/15/2018 | A | PASS |
James Ady
|
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden FInal ok
|
Final | 5/30/2018 | 5/31/2018 | 5/31/2018 | A | PART |
James Ady
|
|
|
Contact: Jay Gooden.... Please call 30 minutes before going so he can meet you there Phone #: ###-#### Inspection requested via web by Deb Gooden 250.104. Water piping bond shall be sized in accordance with 250.102C1. (Main water lines for both fire risers and domestic) 314.20. Boxes set back more than 1/4in shall have spark rings. (All receps in Waynes coating, Plywood and tile) 408.4 Feild identification shall be clear and evident to its specific purpose.(Circuits labeled "Recepts" shall be labeled more specificly) Disc. means shall be readily accessible. (Ice Machines)
|
Electrical Rough-In | 5/31/2018 | 5/31/2018 | 5/31/2018 | P | PASS |
James Ady
|
|
|
Contact: Jay Gooden.... Please call 30 minutes before going so he can meet you there Phone #: ###-#### Inspection requested via web by Deb Gooden rough in ok
|
Electrical Rough-In | 5/22/2018 | 5/23/2018 | 5/23/2018 | A | PASS |
James Ady
|
|
|
Contact: Clay Frienwald... ceiling inspection in the office area please Phone #: ###-#### Inspection requested via web by Deb Gooden Ceiling only ok to cover
|
Electrical Rough-In | 1/10/2018 | 1/11/2018 | 1/11/2018 | A | PASS |
James Ady
|
|
|
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden remote restrooms only ok to cover
|
Electrical Rough-In | 12/14/2017 | 12/15/2017 | 12/15/2017 | A | PASS |
James Ady
|
|
|
Contact: Ryan Mrachek, wall cover inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden office walls and hard lid areas only ok to cover
|
Permanent Service | 12/11/2017 | 12/12/2017 | 12/12/2017 | A | PASS |
James Ady
|
|
|
CONTACT: RYAN MRACHEK... Perm service and Meyers cabinet inspections please Phone #: ###-#### Inspection requested via web by Deb Gooden Meyers cabinet needs seperate permit. Building only p/s u/g n ok
|
Electrical Rough-In | 12/1/2017 | 12/4/2017 | 12/4/2017 | A | PASS |
James Ady
|
|
|
Contact: Ryan Mrachek, Wall cover inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden South exterior wall and demising wall one side only rough in ok
|