Permanent Service | 10/4/2017 | 10/5/2017 | 10/4/2017 | A | CANC |
Tom Saunders
|
|
|
Joe Phone #: ###-####...wrong inspection..finaled 10/4/17
|
Final | 10/4/2017 | 10/4/2017 | 10/4/2017 | P | PASS |
Tom Saunders
|
|
|
Joe Phone #: ###-####...ok to final
|
Permanent Service | 10/3/2017 | 10/4/2017 | 10/4/2017 | A | PASS |
Tom Saunders
|
|
|
Joe Phone #: ###-####...p/s o/h rec ok...pole behind trailer
|
Permanent Service | 10/2/2017 | 10/3/2017 | 10/3/2017 | A | FAIL |
Tom Saunders
|
|
|
Joe Phone #: ###-####...nec 250.56 second ground rod needed 6' apart from first ground rod, ground rod shall be installed 8' into ground at finish grade, open hole in disconnect needs sealed
|