Final | 11/3/2017 | 11/6/2017 | 11/6/2017 | A | PASS |
Eric Story
|
|
|
Michael Donelson ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok signed card
|
Electrical Rough-In | 10/26/2017 | 10/27/2017 | 10/27/2017 | A | PASS |
Eric Story
|
|
|
Michael Donelson ###-#### Above Grid Phone #: ###-#### Inspection requested via web by Samatha Solberg Corrections fixed ceilings only ok to cover
|
Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Michael Donelson ###-#### Above Grid/ceiling inspection Phone #: ###-#### Inspection requested via web by Samatha Solberg 300.15- All cables shall terminate in a box. MC above grid in wellnes room. 314.17(A)- Unused openings shall be sealed. Several connectors left in boxes and open KOs. 314.22(E)- Boxes mounted on support wires shall be secured at both ends and taut. Called contact and left message.
|
Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/25/2017 | A | CANC |
Eric Story
|
|
|
Michael Donelson ###-####. Above Grid/ceiling Phone #: ###-#### >> Inspection requested via web by Samatha Solberg Inspection cancelled from web by: Samatha Solberg
|
Electrical Rough-In | 10/3/2017 | 10/4/2017 | 10/4/2017 | A | PASS |
Eric Story
|
|
|
This is for a rough in wall inspection.Michael Donelson ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Walls only ok to cover
|