Final | 1/4/2018 | 1/4/2018 | 1/4/2018 | P | PASS |
James Ady
|
|
|
Mitch Phone #: ###-#### Corrections made final ok
|
Final | 12/11/2017 | 12/11/2017 | 12/11/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Mitch Phone #: ###-#### 110.3- GFCI in garage opposite wall from panel shows open ground. 110.27- All wiring in unfinished garage walls located below 8' shall be protected from physical damage. Ceiling not 8' so cover wiring up to ceiling in stud bays where exposed. 210.8- GFCI devices shall be located in a readily accessible areas. Eave receptacle located above 6'7".
|
Electrical Rough-In | 11/8/2017 | 11/9/2017 | 11/9/2017 | A | PASS |
Eric Story
|
|
|
underground - MItch Phone #: ###-#### u/g from house to detached garage ok to cover
|