Permit Information
Permit NumberELE17-03433
StatusFinaled
Name TOTAL PRECISION ELECTRIC LLC
Site Address 10671 W TREELINE CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Fire loss rewire except garage. Reusing existing service
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/25/20181/26/20181/26/2018APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Tyler Ridley....corrections made...ok to final
Final1/24/20181/25/20181/25/2018AFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Tyler Ridley...

1) breaker lock oput needs installed on OCPD of dishwasher circuit
2) romex shall be completely protected from physical damage-kit island flex too short
3) where metal flex is used it shall terminate in a box with means of attachment-metal box for island outlet
4) the panel shall be labelled completely and legibily-breakers mark spares are powering circuits
5) down stairs bed nedds outlet installed on 30" wall space-was not completed as per rough in inspection
Electrical Rough-In10/11/201710/12/201710/12/2017APASS
DetailsMark Moncarr
Lift garage door for entry Phone #: ###-#### Inspection requested via web by Tyler Ridley Ok cover. All corrections made. Did not check neutrals in panel.
Electrical Rough-In10/10/201710/11/201710/11/2017AFAIL
DetailsRock A. Hudson
Garage door can be lifted for entry Phone #: ###-#### Inspection requested via web by Tyler Ridley
AFCI protection required for bedroom areas
210.52- Down bed 30" wall shall have receptacle outlet installed for wall space.
300.4- Where NM cable is run thru bored or notched studs that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Master closet, master bath, end of hall.
300.15- All NM cable shall terminate in a box. Fireplace wiring.
300.15(A)(1)- All terminations shall be accessible. Smoke in basement hall not secured and sitting on duct.
334.12- NM cable shall not be installed where subject to damage. Up west bed upper hole will be partially cavered by drywall.
334.30- NM cable shall be supported at intervals not to exceed 4 1/2'. 14-3 for smokes from basement to up bed.
408.41- Grounded conductors shall terminate individually. Contractor called to clearify the termination of grounded and left prior to my return call. Told he could take care of this item by final would be OK