Final | 11/1/2017 | 11/2/2017 | 11/2/2017 | A | PASS |
Rock A. Hudson
|
|
|
012 is the lock box code. Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
Final | 10/31/2017 | 11/1/2017 | 11/1/2017 | A | FAIL |
Rock A. Hudson
|
|
|
There is a lock box at the bottom of the stairs, attached to the railing. The code is 012. Phone #: ###-#### Inspection requested via web by Barbara Szurgot 210.8(B)- All 120 volt receptacle outlets installed with in 6' of a sink shall have GFCI protection. As per print shall comply with 2012 IBC. 2012 International Energy Concervation Code C405.2.2.2- Occupancy sensors shall be installed in all meeting rooms, break room areas, private offices and other areas 300 sq. ft or less. After 30 minutes or less shut off setting. All areas shall have occ sensors installed.
|
Final | 10/31/2017 | 11/1/2017 | 10/31/2017 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot
|
Electrical Rough-In | 10/12/2017 | 10/13/2017 | 10/13/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Space is office space for a BBQ company. Moved misc wiring for removal of wall and new door. Added receptacle outlets. Rough in ok cover
|