Final | 12/27/2017 | 12/27/2017 | 12/27/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Ok final. Corrections made. GFI/AFI recept combo used in basement bed/office.
|
Final | 12/11/2017 | 12/11/2017 | 12/11/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez . 210.12- AFCI protection needed for circuit extension in basement bedroom. Thru door receptacles to right. 314.20- Spark ring needed on basement column to left or box shall be flush. 422.30- A disconnecting means shall be provide for hardwired appliances. 110.15 lockout acceptable.
|
Electrical Rough-In | 10/20/2017 | 10/20/2017 | 10/20/2017 | P | PASS |
James Ady
|
|
|
Please call Tom prior to inspection. Phone #: ###-#### Inspection requested via web by Kevin Perez Kitchen, down bed and living and misc cutin lights through out. Rough in ok
|