Permit Information
Permit NumberELE17-03557
StatusIssued
Name ALL ELECTRIC
Site Address 710 N ORCHARD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Interior service replacement & grounding
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection7/27/20207/27/20207/27/2020 PEND
DetailsDaryl DeGrange
This permit is still open with the City of Boise. Please call 208 ###-#### with progress report or any questions. If this job is complete, please schedule an final inspection online Thank you!
ELE-Aging Inspection4/27/20204/27/20204/27/2020 FAIL
DetailsDaryl DeGrange
Pursuant of contacting aging permit applicants is on hold until required Social Distancing has been removed.
ELE-Aging Inspection1/27/20201/27/20202/4/2020 FAIL
DetailsRock A. Hudson
Waiting on contractor
ELE-Aging Inspection10/28/201910/28/201911/1/2019 FAIL
DetailsRock A. Hudson
Drove by to check if ok to final.
110.24- Available fault current shall be posted with date calculated as noted on permanent service inspection.
Permanent Service11/7/201711/7/201711/7/2017PPASS
DetailsEric Story
Call 30 mins ahead -Mitch Phone #: ###-####
Available fault calc will be posted for final
p/s o/h rec ok
Conference10/23/201710/23/201710/23/2017PDONE
DetailsRock A. Hudson
Mitch Phone #: ###-####
4-05-32 Code violations not to be retained.
4-05-31(C)- Unfused conductors shall not enter a building unless considered outside building as defined in NEC 230.6.
NEC 230.70- A service disconnecting means shall be provided for each service, 1 single phase and 1 3 phase with high leg enters through roof and terminates in panel boards on interior of building. Required labels and high leg marking.