Final | 12/10/2018 | 12/11/2018 | 12/11/2018 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by michael hunt...corrections made...ok to final
|
Final | 11/26/2018 | 11/26/2018 | 11/26/2018 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by michael hunt.... 1..riser shall be strapped within 3ft of meter 2..outlets need added to counterspace dining rm...210.52(C)(1), 210.52(A)(4), 210.52(B)(1)
|
Permanent Service | 11/15/2017 | 11/15/2017 | 11/15/2017 | P | PASS |
Tom Saunders
|
|
|
Idaho power outage if possible inspection closer to noon. Thank you mike Phone #: ###-#### Inspection requested via web by michael hunt... p/s u/g rec ok
|
Rough-In Permanent Service | 10/23/2017 | 10/24/2017 | 10/24/2017 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by michael hunt...rough in inspection only at this time...perm service inspection will need called in later when ready to move meter to new edition and make existing panel a sub panel
|
Electrical Rough-In | 10/24/2017 | 10/24/2017 | 10/24/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by michael hunt...rough of new edition ok to cover, new garage, kitchen, family rm, bonus rm, and patio
|