Electrical Rough-In | 5/24/2018 | 5/25/2018 | 5/25/2018 | A | PASS |
Mark Moncarr
|
|
|
Around 830-900. Looking at EQ plane around short walls. Ok cover. EQ plane installed a long short walls on E and N side. Distance from waters edge is per code.
|
Electrical Rough-In | 5/23/2018 | 5/24/2018 | 5/24/2018 | A | CANC |
Mark Moncarr
|
|
|
Chuck-echo bonding for pool Phone #: ###-#### Re-scheduled for 5/25/18.
|
Conference | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | DONE |
Mark Moncarr
|
|
|
rebar - Chuck Phone #: ###-#### Discussed perimeter bond. 18"-24" out from waters edge, and 4" minimum to 6" maximum below finished grade for burial depth. #8 solid copper needs to be used.
|